01202 725 677Email Us
Product image 1
BS EN12101In Stock

Ventec WS400 AOV Wind Sensor

From£75.00+VAT
Ventec WS400 AOV Wind Sensor
£75.00
Next Day Delivery
30 Day Returns
BS EN12101 Certified
Expert Support
O Range wind input

WS400 — wind sensor for AOV protection

A roof-mounted wind sensor that protects open AOV ventilators from high-wind stress — automatically signalling the O Range panel to close once wind speed exceeds a configurable threshold, with smoke detection always overriding the wind-close command.

WIND MONITORING
Anemometer-type sensing at roof level — closes ventilators when wind exceeds the configured threshold.
HARDWARE PROTECTION
Protects ventilator chassis and actuators from sustained high-wind stress and accelerated wear.
AUTOMATIC RESET
Reopens ventilators once wind speed drops back below threshold — no manual intervention required.
FIRE OVERRIDE
Smoke and fire signals always override the wind-close command — life-safety ventilation is never blocked.
24VDC Operation
100mmDiameter
150gWeight

What it does

The WS400 continuously monitors wind speed at roof level. When sustained wind exceeds the configured setpoint, the unit signals the O Range control panel to close any open ventilators, protecting the actuators and the building fabric from wind stress. As wind drops back below threshold, the panel reopens the ventilators automatically.

The wind setpoint is configurable through O Range Connect and is typically set against the building’s exposure category, height and the actuator manufacturer’s permitted load.

Who it’s for

Specified on all exposed roof-mounted AOV installations — particularly tall buildings, open rural sites and coastal locations where wind loading is a significant operational concern. The WS400 is standard practice for any O Range SHEVS where ventilators remain open for extended periods of day ventilation or overnight purge and require automatic wind protection.

Integration

Connects to the wind sensor input on the O Range control panel. For combined wind and rain protection, pair with the RS 400 rain sensor or upgrade to the W400 weather station — which delivers both signals through a single device and a single wiring run.

Standards & Compliance

  • BS 7346-8 compatible SHEVS
  • BS EN 12101-2 compatible SHEVS
  • O Range panel compatible

Need help specifying your system?

Our UK technical team can review your drawings and recommend the right sensors and panels for your project. Next-day delivery on stocked items.

Call 01202 725 677

Technical Specifications

SpecificationDetail
Dimensions100mm (⌀) x 50mm (H)
Detection PrinciplePhotoelectric
Current Consumption10 amps
Core Type2-Core + ⏚
Weight150g
Detection MethodAnemometer-type wind speed sensing
Operating Voltage24V DC (panel-supplied)
Panel ConnectionWind sensor input — O Range control panel
Override BehaviourOverridden by fire/smoke detection
ThresholdConfigurable wind speed setpoint
StandardsFor use within BS 7346-8 and BS EN 12101-2 compliant SHEVS